STAINLESS STEEL MONITOR WD-19
This multi-model Stainless Steel 304 fire monitor is designed for high-capacity water and foam firefighting. The range extends from PL24 at 24 L/s to PL100 at 100 L/s, with published throw distances increasing from 50 m to 85 m. Each model provides 360° horizontal rotation and vertical movement from -60° to +70°. Rated working pressure varies by model, while the published working pressure range is 0.5–1.6 MPa. PL24 through PL80 use a DN100 or customized installation interface; PL100 is listed with DN125. This monitor is suited to fire-protection systems that require a stainless steel monitor body and a selection of higher flow capacities. Foam operation requires a compatible foam concentrate and proportioning or induction system.
| |
|
Model | PL24 | PL32 | PL40 | PL48 | PL64 | PL80 | PL100 | |
| Flow Rate( L/s) | 24 | 32 | 40 | 48 | 64 | 80 | 100 | |||
| Rated W.P. (MPa) | 1.2 | 1.2 | 1.2 | 1.6 | 1.6 | 1.6 | 1.6 | |||
| W.P.Range(MPa) | 0.5-1.6 | |||||||||
| Distance(m) | 50 | 55 | 60 | 65 | 70 | 80 | 85 | |||
| Angle Of Horizontal Rotation |
360 | |||||||||
| Angle Of Vertical Rotation |
-60—+70 | |||||||||
| Material | Stainless Steel 304 | |||||||||
| Installation Mode | DN100/Or customized | DN125 | ||||||||
| Service Environment | -10℃-+50℃ | |||||||||
Product Highlights
- Stainless Steel 304 monitor body
- Seven flow options from 24 L/s to 100 L/s
- Published throw distance up to 85 m
- 360° horizontal rotation
- -60° to +70° vertical adjustment
- DN100 or customized installation for PL24–PL80
- DN125 installation for PL100
- Operating range from -10°C to +50°C
Application
- High-capacity industrial firefighting
- Oil, fuel and storage-tank protection
- Fire boats, fixed monitors and fire pipelines
- Marine terminals and offshore facilities
- Chemical and process plants
- Firefighting systems requiring Stainless Steel 304 construction
FAQ
Q: What is the maximum flow rate?
A: The PL100 model is published at 100 L/s.
Q: Which model has the longest throw?
A: PL100 has the longest published throw distance at 85 m.
Q: What connection does PL100 use?
A: PL100 is listed with a DN125 installation. Other models are listed as DN100 or customized.
Q: Are all models suitable for foam?
A: The series is a water and foam monitor line, but the foam proportioning system, concentrate and operating parameters must be selected for each installation.